Page 4 - Basic Instrumentation
Notes:
1. These are read only registers.
2. The meaning of the mains, generator and bus phase rotation codes is given in the table below.
3. Registers 95-123 have been added to support the 8680 although not all will be implemented initially.
4. Registers 180 to 192 added to allow mimics of either S1 or S2 load/watts/lead-lag registers according to which side is on load.
Register offset
| Name
| Minimum value
| Maximum value
| Scaling factor
| Units
| Bits/ sign
| 0
| Oil pressure
| 0
| 10000
| 1
| KPa
| 16
| 1
| Coolant temperature
| -50
| 200
| 1
| Degrees C
| 16 S
| 2
| Oil temperature
| -50
| 200
| 1
| Degrees C
| 16 S
| 3
| Fuel level
| 0
| 130
| 1
| %
| 16
| 4
| Charge alternator voltage
| 0
| 40
| 0.1
| V
| 16
| 5
| Battery voltage
| 0
| 40
| 0.1
| V
| 16
| 6
| Engine speed
| 0
| 6000
| 1
| RPM
| 16
| 7
| Generator frequency
| 0
| 70
| 0.1
| Hz
| 16
| 8-9
| Generator L1-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 10-11
| Generator L2-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 12-13
| Generator L3-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 14-15
| Generator L1-L2 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 16-17
| Generator L2-L3 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 18-19
| Generator L3-L1 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 20-21
| Generator L1 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 22-23
| Generator L2 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 24-25
| Generator L3 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 26-27
| Generator earth current
| 0
| 99,999.9
| 0.1
| A
| 32
| 28-29
| Generator L1 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 30-31
| Generator L2 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 32-33
| Generator L3 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 34
| Generator current lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 35
| Mains frequency
| 0
| 70
| 0.1
| Hz
| 16
| 36-37
| Mains L1-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 38-39
| Mains L2-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 40-41
| Mains L3-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 42-43
| Mains L1-L2 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 44-45
| Mains L2-L3 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 46-47
| Mains L3-L1 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 48
| Mains voltage phase lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 49
| Generator phase rotation
| 0
| 3
|
|
| 16
| 50
| Mains phase rotation
| 0
| 3
|
|
| 16
| 51
| Mains current lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 52-53
| Mains L1 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 54-55
| Mains L2 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 56-57
| Mains L3 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 58-59
| Mains earth current
| 0
| 99,999.9
| 0.1
| A
| 32
| 60-61
| Mains L1 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 62-63
| Mains L2 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 64-65
| Mains L3 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 66
| Bus current lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 67
| Bus frequency
| 0
| 70
| 0.1
| Hz
| 16
| 68-69
| Bus L1-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 70-71
| Bus L2-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 72-73
| Bus L3-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 74-75
| Bus L1-L2 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 76-77
| Bus L2-L3 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 78-79
| Bus L3-L1 voltage
| 0
| 30,000
| 0.1
| V
| 32
|
Basic instrumentation continued
Register offset
| Name
| Minimum value
| Maximum value
| Scaling factor
| Units
| Bits/ sign
| 80-81
| Bus L1 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 82-83
| Bus L2 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 84-85
| Bus L3 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 86-87
| Bus earth current
| 0
| 99,999.9
| 0.1
| A
| 32
| 88-89
| Bus L1 watts
| -999,999,999
| 999,999,999
| 1
| W
| 32 S
| 90-91
| Bus L2 watts
| -999,999,999
| 999,999,999
| 1
| W
| 32 S
| 92-93
| Bus L3 watts
| -999,999,999
| 999,999,999
| 1
| W
| 32 S
| 94
| Bus phase rotation
| 0
| 3
|
|
| 16
| 95
| Bus 2 frequency
| 0
| 70
| 0.1
| Hz
| 16
| 96-97
| Bus 2 L1-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 98-99
| Bus 2 L2-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 100-101
| Bus 2 L3-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 102-103
| Bus 2 L1-L2 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 104-105
| Bus 2 L2-L3 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 106-107
| Bus 2 L3-L1 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 108-109
| Bus 2 L1 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 110-111
| Bus 2 L2 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 112-113
| Bus 2 L3 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 114-115
| Bus 2 earth current
| 0
| 99,999.9
| 0.1
| A
| 32
| 116-117
| Bus 2 L1 watts
| -999,999,999
| 999,999,999
| 1
| W
| 32 S
| 118-119
| Bus 2 L2 watts
| -999,999,999
| 999,999,999
| 1
| W
| 32 S
| 120-121
| Bus 2 L3 watts
| -999,999,999
| 999,999,999
| 1
| W
| 32 S
| 122
| Bus 2 phase rotation
| 0
| 3
|
|
| 16
| 123
| Bus 2 current lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 124
| S1 frequency
| 0
| 70
| 0.1
| Hz
| 16
| 125-126
| S1 L1-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 127-128
| S1 L2-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 129-130
| S1 L3-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 131-132
| S1 L1-L2 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 133-134
| S1 L2-L3 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 135-136
| S1 L3-L1 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 137-138
| S1 L1 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 139-140
| S1 L2 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 141-142
| S1 L3 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 143-144
| S1 earth current
| 0
| 99,999.9
| 0.1
| A
| 32
| 145-146
| S1 L1 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 147-148
| S1 L2 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 149-150
| S1 L3 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 151
| S1 current lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 152
| S2 frequency
| 0
| 70
| 0.1
| Hz
| 16
| 153-154
| S2 L1-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 155-156
| S2 L2-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 157-158
| S2 L3-N voltage
| 0
| 18,000
| 0.1
| V
| 32
| 159-160
| S2 L1-L2 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 161-162
| S2 L2-L3 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 163-164
| S2 L3-L1 voltage
| 0
| 30,000
| 0.1
| V
| 32
| 165-166
| S2 L1 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 167-168
| S2 L2 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 169-170
| S2 L3 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 171-172
| S2 earth current
| 0
| 99,999.9
| 0.1
| A
| 32
| 173-174
| S2 L1 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 175-176
| S2 L2 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 177-178
| S2 L3 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 179
| S2 current lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 180-181
| Load L1 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 182-183
| Load L2 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 184-185
| Load L3 current
| 0
| 99,999.9
| 0.1
| A
| 32
| 186-187
| Load L1 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 188-189
| Load L2 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 190-191
| Load L3 watts
| -99,999,999
| 99,999,999
| 1
| W
| 32 S
| 192
| Load current lag/lead
| -180
| +180
| 1
| degrees
| 16 S
| 193
| S1 phase rotation
| 0
| 3
|
|
| 16
| 194
| S2 phase rotation
| 0
| 3
|
|
| 16
| 195-255
| Reserved
|
|
|
|
|
|
Phase rotation codes
Code
| Meaning
| 0
| Indeterminate - the voltage on one or more phase is insufficient to measure the rotation
| 1
| L1 leads L2 which leads L3
| 2
| L3 leads L2 which leads L1
| 3
| Phase error - two or more phase inputs are in phase
| 4-65534
| Reserved
| 65535
| Unimplemented
|
|