Page 9 – Total Harmonic Distortion
Notes:
1. These are read only registers.
2. Only supported on 88xx/84xx modules at present (introduced at version 1.0 of these modules)
3. 8810/8410 don’t support registers 120-131 – they will return Unimplemented (sentinel value)
Registers
Register offset
| Name
| Minimum value
| Maximum value
| Scaling factor
| Units
| Bits/ Sign
|
0
| V1 Voltage L1 THD
| 0
| 10000
| 0.01
| %
| 16
|
1
| V1 Voltage L1 Fundamental level
| 0
| 100
| 1
|
| 16
|
2
| V1 Voltage L1 3rd harmonic level
| 0
| 100
| 1
|
| 16
|
3
| V1 Voltage L1 5th harmonic level
| 0
| 100
| 1
|
| 16
|
4
| V1 Voltage L1 7th harmonic level
| 0
| 100
| 1
|
| 16
|
5
| V1 Voltage L1 9th harmonic level
| 0
| 100
| 1
|
| 16
|
6
| V1 Voltage L1 11th harmonic level
| 0
| 100
| 1
|
| 16
|
7
| V1 Voltage L1 13th harmonic level
| 0
| 100
| 1
|
| 16
|
8
| V1 Voltage L1 15th harmonic level
| 0
| 100
| 1
|
| 16
|
9
| V1 Voltage L1 17th harmonic level
| 0
| 100
| 1
|
| 16
|
10
| V1 Voltage L1 19th harmonic level
| 0
| 100
| 1
|
| 16
|
11
| V1 Voltage L1 21st harmonic level
| 0
| 100
| 1
|
| 16
|
12-23
| V1 Voltage L2 THD etc
|
|
|
|
|
|
24-35
| V1 Voltage L3 THD etc
|
|
|
|
|
|
36-47
| V2 Voltage L1 THD etc
|
|
|
|
|
|
48-59
| V2 Voltage L2 THD etc
|
|
|
|
|
|
60-71
| V2 Voltage L3 THD etc
|
|
|
|
|
|
72-83
| Current L1 THD etc
|
|
|
|
|
|
84-95
| Current L2 THD etc
|
|
|
|
|
|
96-107
| Current L3 THD etc
|
|
|
|
|
|
108-119
| Current Neutral/Earth THD etc
|
|
|
|
|
|
120-131
| Current 5th CT THD etc
|
|
|
|
|
|
132-255
| Reserved
|
|
|
|
|
|
Page 11 - Diagnostic - General
Notes:
4. These are read only registers.
5. Register 0 gives the version as major/minor, with the major version in the upper 8 bits, the minor version in the lower 8 bits.
Registers
Register offset
| Name
| Minimum value
| Maximum value
| Scaling factor
| Units
| Bits/ Sign
|
0
| Software version
| 0
| 9999
| 0.01
|
| 16
|
1
| CPU power usage
| 0
| 200
| 1
| %
| 16
|
2
| Button number pressed, 0=none
| 0
| 255
| 1
|
| 16
|
3
| Backup supply voltage
| 0
| 40
| 0.1
| V
| 16
|
4-255
| Reserved
|
|
|
|
|
|
Page 12 - Diagnostic - Digital Inputs
Notes
1. These are read only registers.
2. These registers represent the state of the actual inputs to the control unit before the application of any time delays or other processing and are intended for diagnostic purposes only.
3. The number of named digital inputs may be increased in future versions of GenComm. Manufacturers may not add their own to the list of named inputs as there are no corresponding strings to identify them. Any inputs that are required but not named must be included in the list of unnamed digital inputs.
4. The meaning of the named digital input codes is shown in the table below.
5. Register 16 indicates the number of unnamed digital inputs that are supported, any software that displays these must cope with any number up to 128. Each is represented by only one bit as there is no need to indicate that it is unimplemented.
6. Unimplemented inputs (including totally unimplemented registers) return 3, not an exception.
Registers
Register offset
| Name
| Minimum value
| Maximum value
| Scaling factor
| Units
| Bits/ Sign
|
0
| Emergency stop input
| 0
| 3
|
|
| 15/16-16/16
|
| Low oil pressure switch input
| 0
| 3
|
|
| 13/16-14/16
|
| High engine temp. switch input
| 0
| 3
|
|
| 11/16-12/16
|
| Remote start input
| 0
| 3
|
|
| 9/16-10/16
|
| Remote fuel on input
| 0
| 3
|
|
| 7/16-8/16
|
| Lamp test input
| 0
| 3
|
|
| 5/16-6/16
|
| Reset input
| 0
| 3
|
|
| 3/16-4/16
|
| Panel lock input
| 0
| 3
|
|
| 1/16-2/16
|
1
| Start button input
| 0
| 3
|
|
| 15/16-16/16
|
| Stop button input
| 0
| 3
|
|
| 13/16-14/16
|
| Transfer to generator button input
| 0
| 3
|
|
| 11/16-12/16
|
| Transfer to mains button input
| 0
| 3
|
|
| 9/16-10/16
|
| Unimplemented
| 3
| 3
|
|
| 7/16-8/16
|
| Unimplemented
| 3
| 3
|
|
| 5/16-6/16
|
| Unimplemented
| 3
| 3
|
|
| 3/16-4/16
|
| Unimplemented
| 3
| 3
|
|
| 1/16-2/16
|
2-15
| Reserved
|
|
|
|
| 16
|
16
| Number of unnamed digital inputs
| 0
| 128
|
|
| 16
|
17
| Unnamed digital input 1
| Open
| Closed
|
|
| 16/16
|
| Unnamed digital input 2
| Open
| Closed
|
|
| 15/16
|
| Unnamed digital input 3
| Open
| Closed
|
|
| 14/16
|
| Unnamed digital input 4
| Open
| Closed
|
|
| 13/16
|
| Unnamed digital input 5
| Open
| Closed
|
|
| 12/16
|
| Unnamed digital input 6
| Open
| Closed
|
|
| 11/16
|
| Unnamed digital input 7
| Open
| Closed
|
|
| 10/16
|
| Unnamed digital input 8
| Open
| Closed
|
|
| 9/16
|
| Unnamed digital input 9
| Open
| Closed
|
|
| 8/16
|
| Unnamed digital input 10
| Open
| Closed
|
|
| 7/16
|
| Unnamed digital input 11
| Open
| Closed
|
|
| 6/16
|
| Unnamed digital input 12
| Open
| Closed
|
|
| 5/16
|
| Unnamed digital input 13
| Open
| Closed
|
|
| 4/16
|
| Unnamed digital input 14
| Open
| Closed
|
|
| 3/16
|
| Unnamed digital input 15
| Open
| Closed
|
|
| 2/16
|
| Unnamed digital input 16
| Open
| Closed
|
|
| 1/16
|
18
| Unnamed digital input 17-32
| Open
| Closed
|
|
| 16
|
19
| Unnamed digital input 33-48
| Open
| Closed
|
|
| 16
|
20
| Unnamed digital input 49-64
| Open
| Closed
|
|
| 16
|
21
| Unnamed digital input 65-80
| Open
| Closed
|
|
| 16
|
22
| Unnamed digital input 81-96
| Open
| Closed
|
|
| 16
|
23
| Unnamed digital input 97-112
| Open
| Closed
|
|
| 16
|
24
| Unnamed digital input 113-128
| Open
| Closed
|
|
| 16
|
25-255
| Reserved
|
|
|
|
|
|
Named digital input codes
Code
| Meaning
|
0
| Open
|
1
| Closed
|
2
| Reserved
|
3
| Unimplemented
|