Notes:

1. These are read only registers.

2. Only supported on 88xx/84xx modules at present (introduced at version 1.0 of these modules)

3. 8810/8410 don’t support registers 120-131 – they will return Unimplemented (sentinel value)

 

Registers

Register offset Name Minimum value Maximum value Scaling factor Units Bits/ Sign
0 V1 Voltage L1 THD 0 10000 0.01 % 16
1 V1 Voltage L1 Fundamental level 0 100 1   16
2 V1 Voltage L1 3rd harmonic level 0 100 1   16
3 V1 Voltage L1 5th harmonic level 0 100 1   16
4 V1 Voltage L1 7th harmonic level 0 100 1   16
5 V1 Voltage L1 9th harmonic level 0 100 1   16
6 V1 Voltage L1 11th harmonic level 0 100 1   16
7 V1 Voltage L1 13th harmonic level 0 100 1   16
8 V1 Voltage L1 15th harmonic level 0 100 1   16
9 V1 Voltage L1 17th harmonic level 0 100 1   16
10 V1 Voltage L1 19th harmonic level 0 100 1   16
11 V1 Voltage L1 21st harmonic level 0 100 1   16
12-23 V1 Voltage L2 THD etc          
24-35 V1 Voltage L3 THD etc          
36-47 V2 Voltage L1 THD etc          
48-59 V2 Voltage L2 THD etc          
60-71 V2 Voltage L3 THD etc          
72-83 Current L1 THD etc          
84-95 Current L2 THD etc          
96-107 Current L3 THD etc          
108-119 Current Neutral/Earth THD etc          
120-131 Current 5th CT THD etc          
132-255 Reserved          

 

 

Page 11 - Diagnostic - General

Notes:

4. These are read only registers.

5. Register 0 gives the version as major/minor, with the major version in the upper 8 bits, the minor version in the lower 8 bits.

 

Registers

Register offset Name Minimum value Maximum value Scaling factor Units Bits/ Sign
0 Software version 0 9999 0.01   16
1 CPU power usage 0 200 1 % 16
2 Button number pressed, 0=none 0 255 1   16
3 Backup supply voltage 0 40 0.1 V 16
4-255 Reserved          

 

 

Page 12 - Diagnostic - Digital Inputs

Notes

1. These are read only registers.

2. These registers represent the state of the actual inputs to the control unit before the application of any time delays or other processing and are intended for diagnostic purposes only.

3. The number of named digital inputs may be increased in future versions of GenComm. Manufacturers may not add their own to the list of named inputs as there are no corresponding strings to identify them. Any inputs that are required but not named must be included in the list of unnamed digital inputs.

4. The meaning of the named digital input codes is shown in the table below.

5. Register 16 indicates the number of unnamed digital inputs that are supported, any software that displays these must cope with any number up to 128. Each is represented by only one bit as there is no need to indicate that it is unimplemented.

6. Unimplemented inputs (including totally unimplemented registers) return 3, not an exception.

 

Registers

Register offset Name Minimum value Maximum value Scaling factor Units Bits/ Sign
0 Emergency stop input 0 3     15/16-16/16
  Low oil pressure switch input 0 3     13/16-14/16
  High engine temp. switch input 0 3     11/16-12/16
  Remote start input 0 3     9/16-10/16
  Remote fuel on input 0 3     7/16-8/16
  Lamp test input 0 3     5/16-6/16
  Reset input 0 3     3/16-4/16
  Panel lock input 0 3     1/16-2/16
1 Start button input 0 3     15/16-16/16
  Stop button input 0 3     13/16-14/16
  Transfer to generator button input 0 3     11/16-12/16
  Transfer to mains button input 0 3     9/16-10/16
  Unimplemented 3 3     7/16-8/16
  Unimplemented 3 3     5/16-6/16
  Unimplemented 3 3     3/16-4/16
  Unimplemented 3 3     1/16-2/16
2-15 Reserved         16
16 Number of unnamed digital inputs 0 128     16
17 Unnamed digital input 1 Open Closed     16/16
  Unnamed digital input 2 Open Closed     15/16
  Unnamed digital input 3 Open Closed     14/16
  Unnamed digital input 4 Open Closed     13/16
  Unnamed digital input 5 Open Closed     12/16
  Unnamed digital input 6 Open Closed     11/16
  Unnamed digital input 7 Open Closed     10/16
  Unnamed digital input 8 Open Closed     9/16
  Unnamed digital input 9 Open Closed     8/16
  Unnamed digital input 10 Open Closed     7/16
  Unnamed digital input 11 Open Closed     6/16
  Unnamed digital input 12 Open Closed     5/16
  Unnamed digital input 13 Open Closed     4/16
  Unnamed digital input 14 Open Closed     3/16
  Unnamed digital input 15 Open Closed     2/16
  Unnamed digital input 16 Open Closed     1/16
18 Unnamed digital input 17-32 Open Closed     16
19 Unnamed digital input 33-48 Open Closed     16
20 Unnamed digital input 49-64 Open Closed     16
21 Unnamed digital input 65-80 Open Closed     16
22 Unnamed digital input 81-96 Open Closed     16
23 Unnamed digital input 97-112 Open Closed     16
24 Unnamed digital input 113-128 Open Closed     16
25-255 Reserved          

 

Named digital input codes

Code Meaning
0 Open
1 Closed
2 Reserved
3 Unimplemented

 