  1. Unimplemented registers within a family/module are shaded
Register offset Name Min value Max value Bits/ Sign 330 331 332 333 334 335
0 Number of unnamed alarm sources 0 256 16 ü ü ü ü ü ü
1 Unnamed digital input A 0 15 13/16-16/16 ü ü ü ü ü ü
  Unnamed digital input B 0 15 9/16-12/16 ü ü ü ü ü ü
  Unnamed digital input C 0 15 5/16-8/16   ü ü ü ü ü
  Unnamed digital input D 0 15 1/16-4/16   ü ü ü ü ü
2 Unnamed digital input E 0 15 13/16-16/16     ü ü ü ü
  Unnamed digital input F 0 15 9/16-12/16     ü ü ü ü
  Unnamed digital input G 0 15 5/16-8/16     ü ü ü ü
  Unnamed digital input H 0 15 1/16-4/16     ü ü ü ü
3 Unnamed digital input I 0 15 13/16-16/16     ü ü ü ü
  Unnamed digital input J 0 15 9/16-12/16     ü ü ü ü
  Unnamed digital input K 0 15 5/16-8/16     ü ü ü ü
  Unnamed digital input L 0 15 1/16-4/16           ü
4 Unimplemented (Reserved for future digital inputs)                  
5 2130 expansion module 0 digital input A 0 15 13/16-16/16           ü
  2130 expansion module 0 digital input B 0 15 9/16-12/16           ü
  2130 expansion module 0 digital input C 0 15 5/16-8/16           ü
  2130 expansion module 0 digital input D 0 15 1/16-4/16           ü
6 2130 expansion module 0 digital input E 0 15 13/16-16/16           ü
  2130 expansion module 0 digital input F 0 15 9/16-12/16           ü
  2130 expansion module 0 digital input G 0 15 5/16-8/16           ü
  2130 expansion module 0 digital input H 0 15 1/16-4/16           ü
7 – 8 2130 expansion module 1 digital inputs A-H                 ü
9 – 10 2130 expansion module 2 digital inputs A-H                  
11-12 2130 expansion module 3 digital inputs A-H                  
13-24 Reserved for expansion modules 4-9 digital inputs                  
25 2130 expansion module 0 analogue input E low 0 15 13/16-16/16           ü
  2130 expansion module 0analogue input E high 0 15 9/16-12/16           ü
  2130 expansion module 0analogue input F low 0 15 5/16-8/16           ü
  2130 expansion module 0analogue input F high 0 15 1/16-4/16           ü
26 2130 expansion module 0 analogue input G low 0 15 13/16-16/16           ü
  2130 expansion module 0analogue input G high 0 15 9/16-12/16           ü
  2130 expansion module 0analogue input H low 0 15 5/16-8/16           ü
  2130 expansion module 0analogue input H high 0 15 1/16-4/16           ü

 

Xx family register allocation continued

Register offset Name Min value Max value Bits/ Sign 330 331 332 333 334 335
27 - 28 2130 expansion module 1 analogue inputs E-H                 ü
29-30 2130 expansion module 2 analogue inputs E-H                  
31-32 2130 expansion module 3 analogue inputs E-H                  
33-44 Unimplemented (Reserved for 2130 expansion module 4-9 analogue inputs E-H)                  
45 PLC function 1 0 15 13/16-16/16           ü
  PLC function 2 0 15 9/16-12/16           ü
  PLC function 3 0 15 5/16-8/16           ü
  PLC function 4 0 15 1/16-4/16           ü
46 PLC function 5 0 15 13/16-16/16           ü
  PLC function 6 0 15 9/16-12/16           ü
  PLC function 7 0 15 5/16-8/16           ü
  PLC function 8 0 15 1/16-4/16           ü
47 PLC function 9 0 15 13/16-16/16           ü
  PLC function 10 0 15 9/16-12/16           ü
  PLC function 11 0 15 5/16-8/16           ü
  PLC function 12 0 15 1/16-4/16           ü
48 PLC function 13 0 15 13/16-16/16           ü
  PLC function 14 0 15 9/16-12/16           ü
  PLC function 15 0 15 5/16-8/16           ü
  PLC function 16 0 15 1/16-4/16           ü
49 PLC function 17 0 15 13/16-16/16           ü
  PLC function 18 0 15 9/16-12/16           ü
  PLC function 19 0 15 5/16-8/16           ü
  PLC function 20 0 15 1/16-4/16           ü
50-64 Unimplemented 0 15 16            
65-255 Reserved                  

 



Exxx register allocation

Register offset Name Min value Maxvalue Bits/ Sign E800 E400
0 Number of unnamed alarm sources Note 12 Note 12 16 ü  
1 Unnamed digital input 1 0 15 13/16-16/16 ü  
  Unnamed digital input 2 0 15 9/16-12/16 ü  
  Unnamed digital input 3 0 15 5/16-8/16 ü  
  Unnamed digital input 4 0 15 1/16-4/16 ü  
2 Unnamed digital input 5 0 15 13/16-16/16 ü  
  Unnamed digital input 6 0 15 9/16-12/16 ü  
  Unnamed digital input 7 0 15 5/16-8/16 ü  
  Unnamed digital input 8 0 15 1/16-4/16 ü  
3 Unnamed digital input 9 0 15 13/16-16/16 ü  
  Unnamed digital input 10 0 15 9/16-12/16 ü  
  Unnamed digital input 11 0 15 5/16-8/16 ü  
  Unnamed digital input 12 0 15 1/16-4/16 ü  
4 Unnamed digital input 13 0 15 13/16-16/16 ü  
  Unnamed digital input 14 0 15 9/16-12/16 ü  
  Unnamed digital input 15 0 15 5/16-8/16 ü  
  Unnamed digital input 16 0 15 1/16-4/16 ü  
5 Flexible Digital Input A 0 15 13/16-16/16 ü  
  Flexible Digital Input B 0 15 9/16-12/16 ü  
  Flexible Digital Input C 0 15 5/16-8/16 ü  
  Flexible Digital Input D 0 15 1/16-4/16 ü  
6 Flexible Digital Input E 0 15 13/16-16/16 ü  
  Flexible Digital Input F 0 15 9/16-12/16 ü  
  Flexible Digital Input G 0 15 5/16-8/16 ü  
  Flexible Digital Input H 0 15 1/16-4/16 ü  
7 Flexible Digital Input I 0 15 13/16-16/16 ü  
  Flexible Digital Input J 0 15 9/16-12/16 ü  
  Flexible Digital Input K 0 15 5/16-8/16 ü  
  Flexible Digital Input L 0 15 1/16-4/16 ü  
8 Unnamed digital input 29 0 15 13/16-16/16 ü  
  Unnamed digital input 30 0 15 9/16-12/16 ü  
  Unnamed digital input 31 0 15 5/16-8/16 ü  
  Unnamed digital input 32 0 15 1/16-4/16 ü  
9 2130 expansion module 0 digital input A 0 15 13/16-16/16 ü  
  2130 expansion module 0 digital input B 0 15 9/16-12/16 ü  
  2130 expansion module 0 digital input C 0 15 5/16-8/16 ü  
  2130 expansion module 0 digital input D 0 15 1/16-4/16 ü  
10 2130 expansion module 0 digital input E 0 15 13/16-16/16 ü  
  2130 expansion module 0 digital input F 0 15 9/16-12/16 ü  
  2130 expansion module 0 digital input G 0 15 5/16-8/16 ü  
  2130 expansion module 0 digital input H 0 15 1/16-4/16 ü  
11-12 2130 expansion module 1 digital input A-H       ü  
13-14 2130 expansion module 2 digital input A-H       ü  
15-16 2130 expansion module 3 digital input A-H       ü  

 

Exxx register allocation (continued)

Register offset Name Min value Maxvalue Bits/ Sign E800
17 2131 expansion module 0 digital input A 0 15 13/16-16/16 ü
  2131 expansion module 0 digital input B 0 15 9/16-12/16 ü
  2131 expansion module 0 digital input C 0 15 5/16-8/16 ü
  2131 expansion module 0 digital input D 0 15 1/16-4/16 ü
18 2131 expansion module 0 digital input E 0 15 13/16-16/16 ü
  2131 expansion module 0 digital input F 0 15 9/16-12/16 ü
  2131 expansion module 0 digital input G 0 15 5/16-8/16 ü
  2131 expansion module 0 digital input H 0 15 1/16-4/16 ü
19 2131 expansion module 0 digital input I 0 15 13/16-16/16 ü
  2131 expansion module 0 digital input J 0 15 9/16-12/16 ü
  2131 expansion module 1 digital input A 0 15 5/16-8/16 ü
  2131 expansion module 1 digital input B 0 15 1/16-4/16 ü
20 2131 expansion module 1 digital input C 0 15 13/16-16/16 ü
  2131 expansion module 1 digital input D 0 15 9/16-12/16 ü
  2131 expansion module 1 digital input E 0 15 5/16-8/16 ü
  2131 expansion module 1 digital input F 0 15 1/16-4/16 ü
21 2131 expansion module 1 digital input G 0 15 13/16-16/16 ü
  2131 expansion module 1 digital input H 0 15 9/16-12/16 ü
  2131 expansion module 1 digital input I 0 15 5/16-8/16 ü
  2131 expansion module 1 digital input J 0 15 1/16-4/16 ü
22 2131 expansion module 2 digital input A 0 15 13/16-16/16 ü
  2131 expansion module 2 digital input B 0 15 9/16-12/16 ü
  2131 expansion module 2 digital input C 0 15 5/16-8/16 ü
  2131 expansion module 2 digital input D 0 15 1/16-4/16 ü
23 2131 expansion module 2 digital input E 0 15 13/16-16/16 ü
  2131 expansion module 2 digital input F 0 15 9/16-12/16 ü
  2131 expansion module 2 digital input G 0 15 5/16-8/16 ü
  2131 expansion module 2 digital input H 0 15 1/16-4/16 ü
24 2131 expansion module 2 digital input I 0 15 13/16-16/16 ü
  2131 expansion module 2 digital input J 0 15 9/16-12/16 ü
  2131 expansion module 3 digital input A 0 15 5/16-8/16 ü
  2131 expansion module 3 digital input B 0 15 1/16-4/16 ü
25 2131 expansion module 3 digital input C 0 15 13/16-16/16 ü
  2131 expansion module 3 digital input D 0 15 9/16-12/16 ü
  2131 expansion module 3 digital input E 0 15 5/16-8/16 ü
  2131 expansion module 3 digital input F 0 15 1/16-4/16 ü
26 2131 expansion module 3 digital input G 0 15 13/16-16/16 ü
  2131 expansion module 3 digital input H 0 15 9/16-12/16 ü
  2131 expansion module 3 digital input I 0 15 5/16-8/16 ü
  2131 expansion module 3 digital input J 0 15 1/16-4/16 ü
27-28 Unimplemented 15 15    
29 2130 expansion module 0 analogue input E low 0 15 13/16-16/16 ü
  2130 expansion module 0analogue input E high 0 15 9/16-12/16 ü
  2130 expansion module 0analogue input F low 0 15 5/16-8/16 ü
  2130 expansion module 0analogue input F high 0 15 1/16-4/16 ü
30 2130 expansion module 0 analogue input G low 0 15 13/16-16/16 ü
  2130 expansion module 0analogue input G high 0 15 9/16-12/16 ü
  2130 expansion module 0analogue input H low 0 15 5/16-8/16 ü
  2130 expansion module 0analogue input H high 0 15 1/16-4/16 ü
31-32 2130 expansion module 1 analogue inputs E-H       ü
33-34 2130 expansion module 2 analogue inputs E-H       ü
35-36 2130 expansion module 3 analogue inputs E-H       ü
37-38 Unimplemented 15 15 16  

 

 

Exxx register allocation (continued)

Register offset Name Min value Maxvalue Bits/ Sign E800
39 Internal flexible sender A analogue input low 0 15 13/16-16/16 ü
  Internal flexible sender A analogue input high 0 15 9/16-12/16 ü
  Internal flexible sender B analogue input low 0 15 5/16-8/16 ü
  Internal flexible sender B analogue input high 0 15 1/16-4/16 ü
40 Internal flexible sender C analogue input low 0 15 13/16-16/16 ü
  Internal flexible sender C analogue input high 0 15 9/16-12/16 ü
  Internal flexible sender D analogue input low 0 15 5/16-8/16 ü
  Internal flexible sender D analogue input high 0 15 1/16-4/16 ü
41 Internal flexible sender E analogue input low 0 15 13/16-16/16 ü
  Internal flexible sender E analogue input high 0 15 9/16-12/16 ü
  Internal flexible sender F analogue input low 0 15 5/16-8/16 ü
  Internal flexible sender F analogue input high 0 15 1/16-4/16 ü
42 Internal flexible sender G analogue input low 0 15 13/16-16/16 ü
  Internal flexible sender G analogue input high 0 15 9/16-12/16 ü
  Internal flexible sender H analogue input low 0 15 5/16-8/16 ü
  Internal flexible sender H analogue input high 0 15 1/16-4/16 ü
43 Internal flexible sender I analogue input low 0 15 13/16-16/16 ü
  Internal flexible sender I analogue input high 0 15 9/16-12/16 ü
  Internal flexible sender J analogue input low 0 15 5/16-8/16 ü
  Internal flexible sender J analogue input high 0 15 1/16-4/16 ü
44 Internal flexible sender K analogue input low 0 15 13/16-16/16 ü
  Internal flexible sender K analogue input high 0 15 9/16-12/16 ü
  Internal flexible sender L analogue input low 0 15 5/16-8/16 ü
  Internal flexible sender L analogue input high 0 15 1/16-4/16 ü
45 Engine Maintenance alarm 1 0 15 13/16-16/16 ü
  Engine Maintenance alarm 2 0 15 9/16-12/16 ü
  Engine Maintenance alarm 3 0 15 5/16-8/16 ü
  Unimplemented 0 15 1/16-4/16  
46 PLC function 1 0 15 13/16-16/16 ü
  PLC function 2 0 15 9/16-12/16 ü
  PLC function 3 0 15 5/16-8/16 ü
  PLC function 4 0 15 1/16-4/16 ü
47 PLC function 5 0 15 13/16-16/16 ü
  PLC function 6 0 15 9/16-12/16 ü
  PLC function 7 0 15 5/16-8/16 ü
  PLC function 8 0 15 1/16-4/16 ü
48 PLC function 9 0 15 13/16-16/16 ü
  PLC function 10 0 15 9/16-12/16 ü
  PLC function 11 0 15 5/16-8/16 ü
  PLC function 12 0 15 1/16-4/16 ü
49 PLC function 13 0 15 13/16-16/16 ü
  PLC function 14 0 15 9/16-12/16 ü
  PLC function 15 0 15 5/16-8/16 ü
  PLC function 16 0 15 1/16-4/16 ü
50 PLC function 17 0 15 13/16-16/16 ü
  PLC function 18 0 15 9/16-12/16 ü
  PLC function 19 0 15 5/16-8/16 ü
  PLC function 20 0 15 1/16-4/16 ü
51 Internal Flexible Sensor A sensor fault 0 15 13/16-16/16 ü
  Internal Flexible Sensor B sensor fault 0 15 9/16-12/16 ü
  Internal Flexible Sensor C sensor fault 0 15 5/16-8/16 ü
  Internal Flexible Sensor D sensor fault 0 15 1/16-4/16 ü
52 Internal Flexible Sensor E sensor fault 0 15 13/16-16/16 ü
  Internal Flexible Sensor F sensor fault 0 15 9/16-12/16 ü
  Internal Flexible Sensor G sensor fault 0 15 5/16-8/16 ü
  Internal Flexible Sensor H sensor fault 0 15 1/16-4/16 ü
53 Internal Flexible Sensor I sensor fault 0 15 13/16-16/16 ü
  Internal Flexible Sensor J sensor fault 0 15 9/16-12/16 ü
  Internal Flexible Sensor K sensor fault 0 15 5/16-8/16 ü
  Internal Flexible Sensor L sensor fault 0 15 1/16-4/16 ü
54-63 Unimplemented 0 15 16  

 

 