Xx/6xxx/L40x/4xxx/45xx MKII family register allocation



Register offset Name Minimum value Maximum value Bits/ Sign
0 Number of unnamed alarm sources 0 256 16
1 Unnamed digital input A 0 15 13/16-16/16
  Unnamed digital input B 0 15 9/16-12/16
  Unnamed digital input C 0 15 5/16-8/16
  Unnamed digital input D 0 15 1/16-4/16
2 Unnamed digital input E 0 15 13/16-16/16
  Unnamed digital input F 0 15 9/16-12/16
  Unnamed analogue input A (Digital) 0 15 5/16-8/16
  Unnamed analogue input B (Digital) 0 15 1/16-4/16
3 Unnamed analogue input C (Digital) 0 15 13/16-16/16
  Reserved for analogue input D (Digital) 0 15 9/16-12/16
  Reserved for analogue input E (Digital) 0 15 5/16-8/16
  Reserved for analogue input F (Digital) 0 15 1/16-4/16
4-44 Unimplemented 0 15 16
45 Flexible Sensor C Low 0 15 13/16-16/16
  Flexible Sensor C High 0 15 9/16-12/16
  Oil Maintenance alarm 0 15 5/16-8/16
  Air Maintenance alarm 0 15 1/16-4/16
46 Fuel Maintenance alarm 0 15 13/16-16/16
  Flexible Sensor D Low 0 15 9/16-12/16
  Flexible Sensor D High 0 15 5/16-8/16
  Flexible Sensor A Low 0 15 1/16-4/16
47 Flexible Sensor A High 0 15 13/16-16/16
  Unimplemented 0 15 9/16-12/16
  Unimplemented 0 15 5/16-8/16
  Unimplemented 0 15 1/16-4/16
48-255 Reserved      

Xx MkII family register allocation

Register offset Name Minimum value

Maximum value

Bits/ Sign
0 Number of unnamed alarm sources 0

256

16
1 Unnamed digital input A 0

15

13/16-16/16
  Unnamed digital input B 0

15

9/16-12/16
  Unnamed digital input C 0

15

5/16-8/16
  Unnamed digital input D 0

15

1/16-4/16
2 Unnamed digital input E 0

15

13/16-16/16
  Unnamed digital input F 0

15

9/16-12/16
  Flex Sender A digital input 0

15

5/16-8/16
  Flex Sender B digital input 0

15

1/16-4/16
3 Flex Sender C digital input 0

15

13/16-16/16
  Flex Sender D digital input 0

15

9/16-12/16
  Reserved for digital input 11 0

15

5/16-8/16
  Reserved for digital input 12 0

15

1/16-4/16
4 Reserved for digital inputs 13-16  

 

 
5 2130 expansion module 0 digital input A 0

15

13/16-16/16
  2130 expansion module 0 digital input B 0

15

9/16-12/16
  2130 expansion module 0 digital input C 0

15

5/16-8/16
  2130 expansion module 0 digital input D 0

15

1/16-4/16
6 2130 expansion module 0 digital input E 0

15

13/16-16/16
  2130 expansion module 0 digital input F 0

15

9/16-12/16
  2130 expansion module 0 digital input G 0

15

5/16-8/16
  2130 expansion module 0 digital input H 0

15

1/16-4/16
7-8 2130 expansion module 1 digital input A-H  

 

 
9-10 Reserved for expansion module 2  

 

 
11-12 Reserved for expansion module 3  

 

 
13-24 Reserved for expansion modules 4-9  

 

 
25 2130 expansion module 0 analogue input E low 0 15

13/16-16/16

  2130 expansion module 0analogue input E high 0 15

9/16-12/16

  2130 expansion module 0analogue input F low 0 15

5/16-8/16

  2130 expansion module 0analogue input F high 0 15

1/16-4/16

26 2130 expansion module 0 analogue input G low 0 15

13/16-16/16

  2130 expansion module 0analogue input G high 0 15

9/16-12/16

  2130 expansion module 0analogue input H low 0 15

5/16-8/16

  2130 expansion module 0analogue input H high 0 15

1/16-4/16

27-28 2130 expansion module 1 analogue inputs E-H  

 

 
29-30 Reserved for expansion module 2  

 

 
31-32 Reserved for expansion module 3  

 

 
33-44 Reserved for 2130 expansion module 4-9 analogue inputs E-H  

 

 
           

 


 


Xx MkII family register allocation continued

45 Flex Sender A analogue input low 0

15

13/16-16/16
  Flex Sender A analogue input high 0

15

9/16-12/16
  Flex Sender B analogue input low 0

15

5/16-8/16
  Flex Sender B analogue input high 0

15

1/16-4/16
46 Flex Sender C analogue input low 0 15

13/16-16/16

  Flex Sender C analogue input high 0 15

9/16-12/16

  Flex Sender D analogue input low 0 15

5/16-8/16

  Flex Sender D analogue input high 0 15

1/16-4/16

47 Maintenance alarm 1 0 15

13/16-16/16

  Maintenance alarm 2 0 15

9/16-12/16

  Maintenance alarm 3 0 15

5/16-8/16

  Unimplemented alarm 0 15

1/16-4/16

48-64 Unimplemented 0 15

16

65-255 Reserved    

 

           


P100 register allocation

The P100 has no unnamed alarms.

Alarm condition codes

Condition Meaning Displayed string
0 Disabled input None
1 Not active alarm None
2 Warning alarm Active string
3 Shutdown alarm Active string
4 Electrical trip alarm Active string
5 Controlled shutdown alarm Active string
6-7 Reserved  
8 Inactive indication (no string) None
9 Inactive indication (displayed string) Inactive string
10 Active indication Active string
11-14 Reserved  
15 Unimplemented alarm None

 

Notes

1) E800 v1.0 to v1.1 uses alarm condition code 4 as a “Controlled Shutdown alarm”


 