59
| 0
| 2133 Expansion module 0 input A (low) string
| UNICODE
| UNICODE
| 512
|
| 32
| 2133 Expansion module 0 input A (high) string
| UNICODE
| UNICODE
| 512
|
| 64
| 2133 Expansion module 0 input B (low) string
| UNICODE
| UNICODE
| 512
|
| 96
| 2133 Expansion module 0 input B (high) string
| UNICODE
| UNICODE
| 512
|
| 128
| 2133 Expansion module 0 input C (low) string
| UNICODE
| UNICODE
| 512
|
| 160
| 2133 Expansion module 0 input C (high) string
| UNICODE
| UNICODE
| 512
|
| 192
| 2133 Expansion module 0 input D (low) string
| UNICODE
| UNICODE
| 512
|
| 224
| 2133 Expansion module 0 input D (high) string
| UNICODE
| UNICODE
| 512
|
60
| 0
| 2133 Expansion module 0 input E (low) string
| UNICODE
| UNICODE
| 512
|
| 32
| 2133 Expansion module 0 input E (high) string
| UNICODE
| UNICODE
| 512
|
| 64
| 2133 Expansion module 0 input F (low) string
| UNICODE
| UNICODE
| 512
|
| 96
| 2133 Expansion module 0 input F (high) string
| UNICODE
| UNICODE
| 512
|
| 128
| 2133 Expansion module 0 input G (low) string
| UNICODE
| UNICODE
| 512
|
| 160
| 2133 Expansion module 0 input G (high) string
| UNICODE
| UNICODE
| 512
|
| 192
| 2133 Expansion module 0 input H (low) string
| UNICODE
| UNICODE
| 512
|
| 224
| 2133 Expansion module 0 input H (high) string
| UNICODE
| UNICODE
| 512
|
61-62
|
| 2133 Expansion module 1 input A-H strings
| UNICODE
| UNICODE
| 512
|
63-64
|
| 2133 Expansion module 1 input A-H strings
| UNICODE
| UNICODE
| 512
|
65-66
|
| 2133 Expansion module 1 input A-H strings
| UNICODE
| UNICODE
| 512
|
Register offset
| Name
| Minimum value
| Maximum value
| Scaling factor
| Units
| Bits/ Sign
| Read/Write
|
| Local bus control (CAN port 0)
|
|
|
|
|
|
|
0
| Device identifier
| 0
| 15
| 1
| 1
| 16
| Read/Write
|
1-31
| Reserved
|
|
|
|
|
|
|
| Miscellaneous
|
|
|
|
|
|
|
32
| Generating set run priority
| 1
| 16
| 1
| 1
| 16
| Read/Write
|
33
| Frequency control offset
| 0
| 1.0
| 0.01
| Hz
| 16
| Read/Write
|
34
| Reserved
| 0
| 0
|
|
| 16
| Read/Write
|
35
| Reserved
| 0
| 0
|
|
| 16
| Read/Write
|
36
| Load level setting (minimum)
| 0
| 100
| 1
| %
| 16
| Read/Write
|
37
| Load level setting (maximum)
| 0
| 100
| 1
| %
| 16
| Read/Write
|
38
| Reserved
| 0
| 0
|
|
| 16S
| Read/Write
|
39
| VAr level setting (maximum)
| -100
| 100
| 1
| %
| 16 S
| Read/Write
|
40
| Bus / Mains load setting
| Bus
| Mains
|
|
| 16
| Read/Write
|
41
| Internal governor IF gain
| 0
| 10
| 0.001
| V
| 16
| Read/Write
|
42
| Internal governor IF offset
| -10
| 10
| 0.001
| V
| 16 S
| Read/Write
|
43
| Internal AVR IF gain
| 0
| 10
| 0.001
| V
| 16
| Read/Write
|
44
| Internal AVR IF offset
| -10
| 10
| 0.001
| V
| 16 S
| Read/Write
|
45
| Commissioning screens enable flag
| 0 (no)
| 1 (yes)
|
|
| 16
| Read/Write
|
46-47
| Reserved
| 0
| 0
|
|
| 16
| Read/Write
|
| Frequency synchroniser
|
|
|
|
|
|
|
48
| Reserved
| 0
| 0
|
|
| 16
| Read/Write
|
49
| Relay pulse rate
| 0.5
| 2.5
| 0.01
| Hz
| 16
| Read/Write
|
50
| Relay pulse length
| 0.1
| 1.6
| 0.1
| Sec
| 16
| Read/Write
|
51
| Gain (proportional gain)
| 0
| 0
|
| %
| 16
| Read/Write
|
52
| Compensation (integral gain)
| 0
| 100
| 1
| %
| 16
| Read/Write
|
52-63
| Reserved
|
|
|
|
|
|
|
| Phase synchroniser
|
|
|
|
|
|
|
64-79
| Reserved
| 0
| 0
|
|
| 16
| Read/Write
|