Архитектура Аудит Военная наука Иностранные языки Медицина Металлургия Метрология
Образование Политология Производство Психология Стандартизация Технологии


Page 8 registers continued



8 Generator failed to close 0

15

13/16-16/16
  Mains failed to close 0

15

9/16-12/16
  Generator failed to open 0

15

5/16-8/16
  Mains failed to open 0

15

1/16-4/16
9 Mains low voltage 0

15

13/16-16/16
  Mains high voltage 0

15

9/16-12/16
  Bus failed to close 0

15

5/16-8/16
  Bus failed to open 0

15

1/16-4/16
10 Mains low frequency 0

15

13/16-16/16
  Mains high frequency 0

15

9/16-12/16
  Mains failed 0

15

5/16-8/16
  Mains phase rotation wrong 0

15

1/16-4/16
11 Generator phase rotation wrong 0

15

13/16-16/16
  Maintenance due 0

15

9/16-12/16
  Clock not set 0

15

5/16-8/16
  Local LCD configuration lost 0

15

1/16-4/16
12 Local telemetry configuration lost 0

15

13/16-16/16
  Control unit not calibrated 0

15

9/16-12/16
  Modem power fault 0

15

5/16-8/16
  Generator short circuit 0

15

1/16-4/16
13 Failure to synchronise 0

15

13/16-16/16
  Bus live 0

15

9/16-12/16
  Scheduled run 0

15

5/16-8/16
  Bus phase rotation wrong 0

15

1/16-4/16
14 Priority selection error 0 15

13/16-16/16

  Multiset communications (MSC) data error 0 15

9/16-12/16

  Multiset communications (MSC) ID error 0 15

5/16-8/16

  Multiset communications (MSC) failure 0 15

1/16-4/16

15 Multiset communications (MSC) too few sets 0 15

13/16-16/16

  Multiset communications (MSC) alarms inhibited 0 15

9/16-12/16

  Multiset communications (MSC) old version units 0 15

5/16-8/16

  Mains reverse power 0 15

1/16-4/16

16 Minimum sets not reached 0 15

13/16-16/16

  Insufficient capacity available 0 15

9/16-12/16

  Expansion input unit not calibrated 0 15

5/16-8/16

  Expansion input unit failure 0 15

1/16-4/16

17 Auxiliary sender 1 low 0 15

13/16-16/16

  Auxiliary sender 1 high 0 15

9/16-12/16

  Auxiliary sender 1 fault 0 15

5/16-8/16

  Auxiliary sender 2 low 0 15

1/16-4/16

18 Auxiliary sender 2 high 0 15

13/16-16/16

  Auxiliary sender 2 fault 0 15

9/16-12/16

  Auxiliary sender 3 low 0 15

5/16-8/16

  Auxiliary sender 3 high 0 15

1/16-4/16

19 Auxiliary sender 3 fault 0 15

13/16-16/16

  Auxiliary sender 4 low 0 15

9/16-12/16

  Auxiliary sender 4 high 0 15

5/16-8/16

  Auxiliary sender 4 fault 0 15

1/16-4/16

20 Engine control unit (ECU) link lost 0 15

13/16-16/16

  Engine control unit (ECU) failure 0 15

9/16-12/16

  Engine control unit (ECU) error 0 15

5/16-8/16

  Low coolant temperature 0 15

1/16-4/16

21 Out of sync 0 15

13/16-16/16

  Low Oil Pressure Switch 0 15

9/16-12/16

  Alternative Auxiliary Mains Fail 0 15

5/16-8/16

  Loss of excitation 0 15

1/16-4/16

           

 

 

Page 8 registers continued

22 Mains kW Limit 0 15 13/16-16/16
  Negative phase sequence 0 15 9/16-12/16
  Mains ROCOF 0 15 5/16-8/16
  Mains vector shift 0 15 1/16-4/16
23 Mains G59 low frequency 0 15 13/16-16/16
  Mains G59 high frequency 0 15 9/16-12/16
  Mains G59 low voltage 0 15 5/16-8/16
  Mains G59 high voltage 0 15 1/16-4/16
24 Mains G59 trip 0 15 13/16-16/16
  Generator kW Overload 0 15 9/16-12/16
  Engine Inlet Temperature high 0 15 5/16-8/16
  Bus 1 live 0 15 1/16-4/16
25 Bus 1 phase rotation wrong 0 15 13/16-16/16
  Bus 2 live 0 15 9/16-12/16
  Bus 2 phase rotation wrong 0 15 5/16-8/16
  Reserved 0 15 1/16-4/16
26-32 Unimplemented      
33-127 Reserved      

 

Page 8 registers continued

128 Number of unnamed digital inputs 0 128 16
129 Unnamed digital input 1 0 15 13/16-16/16
  Unnamed digital input 2 0 15 9/16-12/16
  Unnamed digital input 3 0 15 5/16-8/16
  Unnamed digital input 4 0 15 1/16-4/16
130 Unnamed digital input 5 0 15 13/16-16/16
  Unnamed digital input 6 0 15 9/16-12/16
  Unnamed digital input 7 0 15 5/16-8/16
  Unnamed digital input 8 0 15 1/16-4/16
131 Unnamed digital input 9 0 15 13/16-16/16
  Unnamed digital input 10 0 15 9/16-12/16
  Unnamed digital input 11 0 15 5/16-8/16
  Unnamed digital input 12 0 15 1/16-4/16
132 Unnamed digital input 13 0 15 13/16-16/16
  Unnamed digital input 14 0 15 9/16-12/16
  Unnamed digital input 15 0 15 5/16-8/16
  Unnamed digital input 16 0 15 1/16-4/16
133 Unnamed digital inputs 17-20 0 15 16
134 Unnamed digital inputs 21-24 0 15 16
135 Unnamed digital inputs 25-28 0 15 16
136 Unnamed digital inputs 29-32 0 15 16
137 Unnamed digital inputs 33-36 0 15 16
138 Unnamed digital inputs 37-40 0 15 16
139 Unnamed digital inputs 41-44 0 15 16
140 Unnamed digital inputs 45-48 0 15 16
141 Unnamed digital inputs 49-52 0 15 16
142 Unnamed digital inputs 53-56 0 15 16
143 Unnamed digital inputs 57-60 0 15 16
144 Unnamed digital inputs 61-64 0 15 16
145 Unnamed digital inputs 65-68 0 15 16
146 Unnamed digital inputs 69-72 0 15 16
147 Unnamed digital inputs 73-76 0 15 16
148 Unnamed digital inputs 77-80 0 15 16
149 Unnamed digital inputs 81-84 0 15 16
150 Unnamed digital inputs 85-88 0 15 16
151 Unnamed digital inputs 89-92 0 15 16
152 Unnamed digital inputs 93-96 0 15 16
153 Unnamed digital inputs 97-100 0 15 16
154 Unnamed digital inputs 101-104 0 15 16
155 Unnamed digital inputs 105-108 0 15 16
156 Unnamed digital inputs 109-112 0 15 16
157 Unnamed digital inputs 113-116 0 15 16
158 Unnamed digital inputs 117-120 0 15 16
159 Unnamed digital inputs 121-124 0 15 16
160 Unnamed digital inputs 125-128 0 15 16
161-255 Reserved      

 

 Alarm condition codes

Condition Meaning Displayed string
0 Disabled digital input None
1 Not active alarm None
2 Warning alarm Active string
3 Shutdown alarm Active string
4 Electrical trip alarm Active string
5-7 Reserved  
8 Inactive indication (no string) None
9 Inactive indication (displayed string) Inactive string
10 Active indication Active string
11-14 Reserved  
15 Unimplemented alarm None

 

Notes on alarm codes

1. An alarm that is fitted but disabled by the configuration of the slave device returns code 0.

2. An alarm that is not implemented on a particular control unit returns code 15.

3. An indication that does not require a message to be displayed when inactive returns either code 8 or 10.

4. An indication that does require a message to be displayed when inactive returns either code 9 or 10.

5. The inactive strings are only required for indications, in all other cases they will contain 32 spaces.

 


Поделиться:



Последнее изменение этой страницы: 2019-04-01; Просмотров: 304; Нарушение авторского права страницы


lektsia.com 2007 - 2024 год. Все материалы представленные на сайте исключительно с целью ознакомления читателями и не преследуют коммерческих целей или нарушение авторских прав! (0.022 с.)
Главная | Случайная страница | Обратная связь