| 8
| Generator failed to close
| 0
| 15
| 13/16-16/16
|
|
| Mains failed to close
| 0
| 15
| 9/16-12/16
|
|
| Generator failed to open
| 0
| 15
| 5/16-8/16
|
|
| Mains failed to open
| 0
| 15
| 1/16-4/16
|
| 9
| Mains low voltage
| 0
| 15
| 13/16-16/16
|
|
| Mains high voltage
| 0
| 15
| 9/16-12/16
|
|
| Bus failed to close
| 0
| 15
| 5/16-8/16
|
|
| Bus failed to open
| 0
| 15
| 1/16-4/16
|
| 10
| Mains low frequency
| 0
| 15
| 13/16-16/16
|
|
| Mains high frequency
| 0
| 15
| 9/16-12/16
|
|
| Mains failed
| 0
| 15
| 5/16-8/16
|
|
| Mains phase rotation wrong
| 0
| 15
| 1/16-4/16
|
| 11
| Generator phase rotation wrong
| 0
| 15
| 13/16-16/16
|
|
| Maintenance due
| 0
| 15
| 9/16-12/16
|
|
| Clock not set
| 0
| 15
| 5/16-8/16
|
|
| Local LCD configuration lost
| 0
| 15
| 1/16-4/16
|
| 12
| Local telemetry configuration lost
| 0
| 15
| 13/16-16/16
|
|
| Control unit not calibrated
| 0
| 15
| 9/16-12/16
|
|
| Modem power fault
| 0
| 15
| 5/16-8/16
|
|
| Generator short circuit
| 0
| 15
| 1/16-4/16
|
| 13
| Failure to synchronise
| 0
| 15
| 13/16-16/16
|
|
| Bus live
| 0
| 15
| 9/16-12/16
|
|
| Scheduled run
| 0
| 15
| 5/16-8/16
|
|
| Bus phase rotation wrong
| 0
| 15
| 1/16-4/16
|
| 14
| Priority selection error
| 0
| 15
| 13/16-16/16
|
|
| Multiset communications (MSC) data error
| 0
| 15
| 9/16-12/16
|
|
| Multiset communications (MSC) ID error
| 0
| 15
| 5/16-8/16
|
|
| Multiset communications (MSC) failure
| 0
| 15
| 1/16-4/16
|
| 15
| Multiset communications (MSC) too few sets
| 0
| 15
| 13/16-16/16
|
|
| Multiset communications (MSC) alarms inhibited
| 0
| 15
| 9/16-12/16
|
|
| Multiset communications (MSC) old version units
| 0
| 15
| 5/16-8/16
|
|
| Mains reverse power
| 0
| 15
| 1/16-4/16
|
| 16
| Minimum sets not reached
| 0
| 15
| 13/16-16/16
|
|
| Insufficient capacity available
| 0
| 15
| 9/16-12/16
|
|
| Expansion input unit not calibrated
| 0
| 15
| 5/16-8/16
|
|
| Expansion input unit failure
| 0
| 15
| 1/16-4/16
|
| 17
| Auxiliary sender 1 low
| 0
| 15
| 13/16-16/16
|
|
| Auxiliary sender 1 high
| 0
| 15
| 9/16-12/16
|
|
| Auxiliary sender 1 fault
| 0
| 15
| 5/16-8/16
|
|
| Auxiliary sender 2 low
| 0
| 15
| 1/16-4/16
|
| 18
| Auxiliary sender 2 high
| 0
| 15
| 13/16-16/16
|
|
| Auxiliary sender 2 fault
| 0
| 15
| 9/16-12/16
|
|
| Auxiliary sender 3 low
| 0
| 15
| 5/16-8/16
|
|
| Auxiliary sender 3 high
| 0
| 15
| 1/16-4/16
|
| 19
| Auxiliary sender 3 fault
| 0
| 15
| 13/16-16/16
|
|
| Auxiliary sender 4 low
| 0
| 15
| 9/16-12/16
|
|
| Auxiliary sender 4 high
| 0
| 15
| 5/16-8/16
|
|
| Auxiliary sender 4 fault
| 0
| 15
| 1/16-4/16
|
| 20
| Engine control unit (ECU) link lost
| 0
| 15
| 13/16-16/16
|
|
| Engine control unit (ECU) failure
| 0
| 15
| 9/16-12/16
|
|
| Engine control unit (ECU) error
| 0
| 15
| 5/16-8/16
|
|
| Low coolant temperature
| 0
| 15
| 1/16-4/16
|
| 21
| Out of sync
| 0
| 15
| 13/16-16/16
|
|
| Low Oil Pressure Switch
| 0
| 15
| 9/16-12/16
|
|
| Alternative Auxiliary Mains Fail
| 0
| 15
| 5/16-8/16
|
|
| Loss of excitation
| 0
| 15
| 1/16-4/16
|
| | | | | | |
| 128
| Number of unnamed digital inputs
| 0
| 128
| 16
|
| 129
| Unnamed digital input 1
| 0
| 15
| 13/16-16/16
|
|
| Unnamed digital input 2
| 0
| 15
| 9/16-12/16
|
|
| Unnamed digital input 3
| 0
| 15
| 5/16-8/16
|
|
| Unnamed digital input 4
| 0
| 15
| 1/16-4/16
|
| 130
| Unnamed digital input 5
| 0
| 15
| 13/16-16/16
|
|
| Unnamed digital input 6
| 0
| 15
| 9/16-12/16
|
|
| Unnamed digital input 7
| 0
| 15
| 5/16-8/16
|
|
| Unnamed digital input 8
| 0
| 15
| 1/16-4/16
|
| 131
| Unnamed digital input 9
| 0
| 15
| 13/16-16/16
|
|
| Unnamed digital input 10
| 0
| 15
| 9/16-12/16
|
|
| Unnamed digital input 11
| 0
| 15
| 5/16-8/16
|
|
| Unnamed digital input 12
| 0
| 15
| 1/16-4/16
|
| 132
| Unnamed digital input 13
| 0
| 15
| 13/16-16/16
|
|
| Unnamed digital input 14
| 0
| 15
| 9/16-12/16
|
|
| Unnamed digital input 15
| 0
| 15
| 5/16-8/16
|
|
| Unnamed digital input 16
| 0
| 15
| 1/16-4/16
|
| 133
| Unnamed digital inputs 17-20
| 0
| 15
| 16
|
| 134
| Unnamed digital inputs 21-24
| 0
| 15
| 16
|
| 135
| Unnamed digital inputs 25-28
| 0
| 15
| 16
|
| 136
| Unnamed digital inputs 29-32
| 0
| 15
| 16
|
| 137
| Unnamed digital inputs 33-36
| 0
| 15
| 16
|
| 138
| Unnamed digital inputs 37-40
| 0
| 15
| 16
|
| 139
| Unnamed digital inputs 41-44
| 0
| 15
| 16
|
| 140
| Unnamed digital inputs 45-48
| 0
| 15
| 16
|
| 141
| Unnamed digital inputs 49-52
| 0
| 15
| 16
|
| 142
| Unnamed digital inputs 53-56
| 0
| 15
| 16
|
| 143
| Unnamed digital inputs 57-60
| 0
| 15
| 16
|
| 144
| Unnamed digital inputs 61-64
| 0
| 15
| 16
|
| 145
| Unnamed digital inputs 65-68
| 0
| 15
| 16
|
| 146
| Unnamed digital inputs 69-72
| 0
| 15
| 16
|
| 147
| Unnamed digital inputs 73-76
| 0
| 15
| 16
|
| 148
| Unnamed digital inputs 77-80
| 0
| 15
| 16
|
| 149
| Unnamed digital inputs 81-84
| 0
| 15
| 16
|
| 150
| Unnamed digital inputs 85-88
| 0
| 15
| 16
|
| 151
| Unnamed digital inputs 89-92
| 0
| 15
| 16
|
| 152
| Unnamed digital inputs 93-96
| 0
| 15
| 16
|
| 153
| Unnamed digital inputs 97-100
| 0
| 15
| 16
|
| 154
| Unnamed digital inputs 101-104
| 0
| 15
| 16
|
| 155
| Unnamed digital inputs 105-108
| 0
| 15
| 16
|
| 156
| Unnamed digital inputs 109-112
| 0
| 15
| 16
|
| 157
| Unnamed digital inputs 113-116
| 0
| 15
| 16
|
| 158
| Unnamed digital inputs 117-120
| 0
| 15
| 16
|
| 159
| Unnamed digital inputs 121-124
| 0
| 15
| 16
|
| 160
| Unnamed digital inputs 125-128
| 0
| 15
| 16
|
| 161-255
| Reserved
|
|
|
|
1. An alarm that is fitted but disabled by the configuration of the slave device returns code 0.
2. An alarm that is not implemented on a particular control unit returns code 15.
3. An indication that does not require a message to be displayed when inactive returns either code 8 or 10.
4. An indication that does require a message to be displayed when inactive returns either code 9 or 10.
5. The inactive strings are only required for indications, in all other cases they will contain 32 spaces.