Справочные данные по силовому электрооборудованию
Таблица 8
Трехфазные двухобмоточные трансформаторы 110 кВ
Тип трансформатора
| Sном, МВА
| Пределы регулиро-вания, %
±n× Д
| Каталожные данные
| Расчетные данные
| Uном обмоток кВ
| uк, %
| Δ Рк, кВт
| Δ Рх, кВт
| Iх, %
| R, Ом
| X, Ом
| Δ Qх, кВАр
| В
| Н
| ТМН-2500/110
| 2, 5
| ±10× 1, 50
|
| 6, 6; 11
| 10, 5
|
| 5, 5
| 1, 5
| 42, 6
|
| 37, 5
| ТМН-6300/110
| 6, 3
| ±8× 1, 50
|
| 6, 6; 11
|
| 11, 5
| 0, 8
| 14, 7
|
| 50, 4
| ТДН-10000/110
|
| ±9× 1, 78
|
| 6, 6; 11
|
|
| 0, 7
| 7, 95
|
|
| ТДН-16000/110
|
| ±9× 1, 78
|
| 6, 6; 11
|
|
| 0, 7
| 4, 38
| 86, 7
|
| ТРДН-25000/110
|
| ±9× 1, 78
|
| 6, 3/6, 3; 6, 3/10, 5; 10, 5/10, 5
|
|
| 0, 7
| 2, 54
| 55, 9
|
| ТРДН-32000/110
|
| ±9× 1, 78
|
| 6, 3/6, 3; 6, 3/10, 5; 10, 5/10, 5
|
|
| 0, 75
| 1, 87
| 43, 4
|
| ТРДН-40000/110
|
| ±9× 1, 78
|
| 6, 3/6, 3; 6, 3/10, 5; 10, 5/10, 5
|
|
| 0, 7
| 1, 44
| 34, 8
|
| ТД-40000/110
|
| ±2× 2, 50
|
| 3, 15; 6, 3; 10, 5
|
|
| 0, 7
| 1, 46
| 38, 4
|
| ТРДН-63000/110
|
| ±9× 1, 78
|
| 6, 3/6, 3; 6, 3/10, 5; 10, 5/10, 5
|
|
| 0, 65
| 0, 87
|
|
| ТРДЦНК-80000/110
|
| ±9× 1, 78
|
| 6, 3/6, 3; 6, 3/10, 5; 10, 5/10, 5
|
|
| 0, 6
| 0, 8
|
|
| ТДЦ-80000/110
|
| ±2× 2, 50
|
| 6, 3; 10, 5; 13, 8
|
|
| 0, 6
| 0, 71
| 19, 2
|
| ТРДЦН-80000/110
|
| ±9× 1, 78
|
| 6, 3/6, 3; 6, 3/10, 5; 10, 5/10, 5
|
|
| 0, 6
| 0, 6
| 17, 4
|
| ТРДЦН-25000/110
|
| ±9× 1, 78
|
| 10, 5/10, 5
|
|
| 0, 55
| 0, 4
| 11, 1
| 687, 5
| ТДЦ-125000/110
|
| ±2× 2, 50
|
| 10, 5; 13, 8
|
|
| 0, 55
| 0, 37
| 12, 3
| 687, 5
| ТДЦ-200000/110
|
| ±2× 2, 50
|
| 13, 8; 15, 75; 18
|
|
| 0, 5
| 0, 23
| 7, 7
|
| ТДЦ-250000/110
|
| ±2× 2, 50
|
| 15, 75
|
|
| 0, 5
| 0, 15
| 6, 1
|
| ТДЦ-400000/110
|
| ±2× 2, 50
|
|
|
|
| 0, 45
| 0, 08
| 3, 8
|
| Таблица 9
Тип трансформатора
| Номинальное напряжение обмоток, кВ
| Напряжение Uк между обмотками (в зависимости от положения переключателя РПН) для минимального, среднего и максимального значений регулируемого напряжения, %
| Значения X(1)*В обмоток высшего напряжения
| ВН
| НН
| min
| ср
| max
| ТДН-10000/110
|
| 6, 6; 11, 0
| 8, 70
| 10, 5
| 12, 36
| 0, 176
| ТДН-16000/110
|
| 6, 6; 11, 0
| 9, 80
| 10, 5
| 11, 71
| 0, 182
| ТРДН-25000/110
|
| 6, 3-6, 3; 10, 5-10, 5; 6, 3-10, 5
| 9, 84
| 10, 5
| 11, 72
| 0, 171
| ТРДН-32000/110
|
| 6, 3-6, 3; 10, 5-10, 5; 6, 3-10, 5
| 9, 77
| 10, 5
| 11, 58
| 0, 171
| ТРДН-40000/110
|
| 6, 3-6, 3; 10, 5-10, 5; 6, 3-10, 5
| 9, 59
| 10, 5
| 11, 46
| 0, 171
| ТРДЦН-63000/110
|
| 6, 3-6, 3; 10, 5-10, 5; 6, 3-10, 5
| 10, 84
| 10, 5
| 11, 90
| 0, 171
| ТРДЦН-80000/110
|
| 6, 3-6, 3; 10, 5-10, 5; 6, 3-10, 5
| 9, 76
| 10, 5
| 11, 60
| 0, 236
| ТДЦН-80000/110
|
| 38, 5
| 9, 76
| 10, 5
| 11, 60
| 0, 236
| ТРДЦН-125000/110
|
| 10, 5-10, 5
| 10, 50
| 10, 5
| 11, 90
| 0, 236
| ТДН-16000/150
|
| 6, 6; 11, 0
| 11, 50
| 11, 0
| 11, 80
| 0, 175
| ТРДН-32000/150
|
| 6, 3-6, 3; 10, 5-10, 5; 10, 5-6, 3
| 10, 86
| 10, 5
| 10, 14
| 0, 171
| ТРДН-63000/150
|
| 6, 3-6, 3; 10, 5-10, 5; 10, 5-6, 3
| 10, 66
| 10, 5
| 10, 00
| 0, 171
| ТРДН-32000/220
|
| 6, 6-6, 6; 11-11; 6, 6-11
| 11, 60
| 12, 0
| 12, 70
| 0, 182
| ТРДН-32000/220
|
| 38, 5
| 11, 60
| 12, 0
| 12, 70
| 0, 182
| ТРДЦН-63000/220
|
| 6, 6-6, 6; 11-11; 6, 6-11
| 11, 60
| 12, 0
| 12, 70
| 0, 182
| ТРДЦН-63000/220
|
| 38, 5
| 11, 60
| 12, 0
| 12, 70
| 0, 182
| ТРДЦН-100000/220
|
| 11-11
| 11, 60
| 12, 0
| 12, 70
| 0, 247
| ТРДЦН-100000/220
|
| 38, 5
| 11, 60
| 12, 0
| 12, 70
| 0, 247
| ТРДЦН-160000/220
|
| 11-11
| 11, 30
| 12, 0
| 13, 20
| 0, 247
| ТРДЦН-160000/220
|
| 38, 5
| 11, 30
| 12, 0
| 13, 20
| 0, 247
| ТРДН-63000/330
|
| 6, 3-6, 3; 6, 3-10, 5; 10, 5-10, 5
| 14, 30
| 11, 0
| 8, 80
| 0, 175
| ТДН-63000/330
|
| 38, 5
| 14, 30
| 11, 0
| 8, 80
| 0, 175
| Примечания: 1. Таблица составлена по данным ГОСТ и ТУ, действительным на 1 июня 1987г., и материалам Южного отделения ЭСП.
2. Трансформаторы с высшим напряжением 110кВ выполнены по ГОСТ 12965-74, 150кВ – по ГОСТ 17546-72, 220кВ – по ГОСТ 15957-70, 330кВ – по ГОСТ 17545-72.
Таблица 10
Тип трансформатора
| Номинальное напряжение обмоток, кВ
| Напряжение Uк между обмотками (в зависимости от положения переключателя РПН) для минимального, среднего и максимального значений регулируемого напряжения, %
| Значения X(1)*В обмоток
| ВН
| СН
| НН
| ВН – НН
| ВН – СН
| ВН – СН
| ВН
| СН
| min
| ср
| max
| min
| ср
| max
| min
| ср
| max
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ТДТН-10000/110/35
|
| 38, 5
| 6, 6; 11, 0
| 16, 66
| 17, 0
| 19, 5
| -
| 6, 0
| -
| 9, 99
| 10, 5
| 12, 69
| 0, 193
| 0, 139
| ТДТН-16000/110/35
|
| 38, 5
| 6, 6; 11, 0
| 16, 4
| 17, 0
| 18, 5
| -
| 6, 0
| -
| 9, 5
| 10, 5
| 11, 69
| 0, 216
| 0, 141
| ТДТН-16000/110/35*
|
| 38, 5
| 6, 6; 11, 0
| 9, 58
| 10, 5
| 11, 79
| -
| 6, 0
| -
| 16, 48
| 17, 0
| 18, 58
| 0, 214
| 0, 078
| ТДТН-25000/110/10
|
| 11, 0
| 6, 6
| 17, 47
| 17, 5
| 19, 5
| -
| 6, 5
| -
| 9, 99
| 10, 5
| 11, 86
| 0, 219
| 0, 141
| ТДТН-25000/110/35
|
| 38, 5
| 6, 6; 11, 0
| 17, 47
| 17, 5
| 19, 5
| -
| 6, 5
| -
| 9, 99
| 10, 5
| 11, 86
| 0, 236
| 0, 159
| ТДТН-40000/110/10
|
| 11, 0
| 6, 6
| 17, 04
| 17, 5
| 19, 29
| -
| 6, 5
| -
| 9, 52
| 10, 5
| 11, 56
| 0, 245
| 0, 171
| ТДТН-40000/110/35
|
| 38, 5
| 6, 6; 11, 0
| 17, 04
| 17, 5
| 19, 29
| -
| 6, 5
| -
| 9, 52
| 10, 5
| 11, 56
| 0, 245
| 0, 171
| ТДТН-40000/110/10*
|
| 11, 0
| 6, 6
| 9, 5
| 10, 5
| 11, 6
| -
| 6, 5
| -
| 17, 03
| 17, 5
| 19, 3
| 0, 246
| 0, 115
| ТДТН-40000/110/35*
|
| 38, 5
| 6, 6; 11, 0
| 9, 5
| 10, 5
| 11, 6
| -
| 6, 5
| -
| 17, 03
| 17, 5
| 19, 3
| 0, 246
| 0, 115
| ТДТН-63000/110/10
|
| 11, 0
| 6, 6
| 17, 14
| 17, 5
| 19, 2
| -
| 7, 0
| -
| 10, 1
| 10, 5
| 10, 9
| 0, 258
| 0, 159
| ТДТН-63000/110/35
|
| 38, 5
| 6, 6; 11, 0
| 17, 14
| 17, 5
| 19, 2
| -
| 7, 0
| -
| 10, 1
| 10, 5
| 10, 9
| 0, 258
| 0, 159
| ТДТН-63000/110/10*
|
| 11, 0
| 6, 6
| 10, 1
| 10, 5
| 11, 9
| -
| 7, 0
| -
| 17, 2
| 17, 5
| 19, 3
| 0, 241
| 0, 110
| ТДТН-63000/100/35*
|
| 38, 5
| 6, 6; 11, 0
| 10, 1
| 10, 5
| 11, 9
| -
| 7, 0
| -
| 17, 2
| 17, 5
| 19, 3
| 0, 241
| 0, 110
| ТДТН-80000/110/10
|
| 11, 0
| 6, 6
| 18, 25
| 18, 5
| 20, 47
| -
| 7, 0
| -
| 10, 28
| 11, 0
| 12, 33
| 0, 295
| 0, 151
| ТДТН-80000/110/35
|
| 38, 5
| 6, 6; 11, 0
| 18, 25
| 18, 5
| 20, 47
| -
| 7, 0
| -
| 10, 28
| 11, 0
| 12, 33
| 0, 295
| 0, 151
| ТДТН-80000/110/10*
|
| 11, 0
| 6, 6
| 10, 22
| 11, 0
| 12, 13
| -
| 7, 0
| -
| 18, 15
| 18, 5
| 20, 27
| 0, 295
| 0, 107
| ТДТН-63000/110/35*
|
| 38, 5
| 6, 6; 11, 0
| 10, 22
| 11, 0
| 12, 13
| -
| 7, 0
| -
| 18, 15
| 18, 5
| 20, 27
| 0, 295
| 0, 107
| ТДТН-16000/150/35
|
| 38, 5
| 6, 6; 11, 0
| 18, 27
| 18, 0
| 17, 23
| -
| 6, 0
| -
| 11, 41
| 10, 5
| 10, 38
| 0, 227
| 0, 144
| ТДТН-25000/150/35
|
| 38, 5
| 6, 6; 11, 0
| 18, 5
| 18, 0
| 17, 42
| -
| 6, 0
| -
| 11, 42
| 10, 5
| 10, 4
| 0, 227
| 0, 144
| ТДТН-40000/150/35
|
| 38, 5
| 6, 6; 11, 0
| 18, 57
| 18, 0
| 17, 77
| -
| 6, 0
| -
| 11, 12
| 10, 5
| 10, 25
| 0, 227
| 0, 144
| ТДТН-63000/150/35
|
| 38, 5
| 6, 6; 11, 0
| 18, 3
| 18, 0
| 17, 3
| -
| 6, 0
| -
| 10, 99
| 10, 5
| 10, 13
| 0, 227
| 0, 144
| ТДТН-25000/220/35
|
| 22; 38, 5
| 6, 6; 11, 0
| 19, 5
| 20, 0
| 20, 4
| -
| 6, 5
| -
| 12, 4
| 12, 5
| 13, 4
| 0, 242
| 0, 147
| ТДТН-40000/220/35
|
| 22; 38, 5
| 6, 6; 11, 0
| 29, 3
| 22, 0
| 19, 0
| -
| 9, 5
| -
| 16, 8
| 12, 5
| 9, 8
| 0, 257
| 0, 169
| ТДТН-40000/220/35**
|
| 22; 38, 5
| 6, 6; 11, 0
| 18, 6
| 12, 5
| 9, 9
| -
| 9, 5
| -
| 28, 5
| 22, 0
| 19, 2
| 0, 257
| 0, 132
| ТДЦТН-63000/220/35
|
| 22; 38, 5
| 6, 6; 11, 0
| 30, 4
|
| 19, 7
| -
| 10, 5
| -
| 17, 9
| 12, 5
| 10, 5
| 0, 271
| 0, 176
| ТДЦТН-63000/220/35**
|
| 22; 38, 5
| 6, 6; 11, 0
| 17, 7
| 12, 5
| 10, 4
| -
| 10, 5
| -
| 29, 6
| 24, 0
| 20, 0
| 0, 271
| 0, 142
| Продолжение табл. 10
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| АТДТД-32000/220/110
|
|
| 6, 6; 11, 0; 38, 5
| -
| 34, 0
| -
| 22, 5
| 21, 0
| 23, 0
| 20, 0
| 11, 0
| 7, 0
| 0, 346
| 0, 252
| АТДЦТН-63000/220/110
|
|
| 6, 6; 11, 0; 38, 5
| -
| 35, 0
| -
| 24, 5
| 22, 0
| 25, 0
| 21, 0
| 11, 0
| 7, 0
| 0, 353
| 0, 260
| АТДЦТН-125000/220/110
|
|
| 6, 6; 11, 0; 13, 8; 38, 5
| -
| 31, 0
| -
| 20, 3
| 19, 0
| 20, 1
| 18, 9
| 11, 0
| 6, 8
| 0, 559
| 0, 476
| АТДЦТН-200000/220/110
|
|
| 6, 6; 11, 0; 13, 8; 15, 75; 38, 5
| -
| 32, 0
| -
| 21, 5
| 20, 0
| 21, 2
| 19, 4
| 11, 0
| 6, 7
| 0, 548
| 0, 472
| АТДЦТН-250000/220/110
|
|
| 11, 0; 13, 8; 15, 75; 38, 5
| -
| 32, 0
| -
| 23, 0
| 20, 0
| 21, 8
| 20, 9
| 11, 0
| 7, 1
| 0, 544
| 0, 485
| АТДЦТН-125000/330/110
|
|
| 6, 6; 11, 0; 15, 75; 38, 5
| -
| 35, 0
| -
| 29, 6
| 22, 0
| 22, 1
| 10, 3
| 10, 0
| 10, 8
| 0, 462
| 0, 260
| АТДЦТН-200000/330/110
|
|
| 6, 6; 11, 0; 15, 75; 38, 5
| -
| 34, 0
| -
| 27, 2
| 22, 5
| 20, 3
| 10, 6
| 10, 0
| 11, 0
| 0, 471
| 0, 380
| АТДЦТН-125000/500/110
|
|
| 6, 6; 11, 0; 38, 5
| 26, 0
| 24, 0
| 23, 0
| 16, 0
| 13, 0
| 11, 0
| -
| 10, 5
| -
| -
| -
| АТДЦТН-250000/500/110
|
|
| 11, 0; 38, 5
| 26, 0
| 24, 0
| 23, 0
| 16, 0
| 13, 0
| 11, 0
| -
| 10, 5
| -
| -
| -
| АОДЦТН-167000/500/220
| 500/√ 3
| 230/√ 3
| 11, 0; 13, 8; 15, 75; 20, 0; 38, 5
| -
| 35, 0
| -
| 25, 0
| 21, 5
| 20, 0
| 12, 0
| 11, 0
| 12, 0
| -
| -
| АОДЦТН-267000/500/220
| 500/√ 3
| 230/√ 3
| 11, 0; 13, 8; 15, 75; 20, 0; 38, 5
| -
| 23, 0
| -
| 13, 0
| 12, 5
| 12, 5
| 9, 0
| 8, 5
| 9, 5
| 0, 483
| -
| АОДЦТН-167000/500/330
| 500/√ 3
| 330/√ 3
| 11, 0; 38, 5
| -
| 67, 0
| -
| 77, 0
| 61, 0
| 52, 0
| 13, 5
| 9, 5
| 10, 0
| -
| -
| АОДЦТН-333000/750/330
| 750/√ 3
| 330/√ 3
| 15, 75
| -
| 28, 0
| -
| 27, 0
| 17, 0
| 17, 0
| 12, 0
| 10, 0
| 11, 0
| 0, 412
| -
| АОДЦТН-417000/750/500
| 750/√ 3
| 330/√ 3
| 15, 75
| 92, 0
| 81, 0
| 75, 0
| 70, 0
| 68, 0
| 69, 0
| 13, 0
| 11, 5
| 10, 8
|
| -
| Примечания: 1. Таблица составлена по данным ГОСТ и ТУ, действительным на 1 июня 1987 г. и материалам Южного отделения ЭСП.
2. Звездочкой (*) обозначены трансформаторы, выполненные по варианту п.4 примечания к табл. 5 ГОСТ 12965-74.
3. Двумя звездочками (**) обозначены трансформаторы, выполненные по варианту п.2 примечания к табл. 7 ГОСТ 15957-70.
4. Трансформаторы (автотрансформаторы) с высшим напряжением 110 кВ выполнены по ГОСТ 12965-74; 150 кВ – по ГОСТ 17546-72; 220 кВ – по ГОСТ 15957-70; 330 кВ – по ГОСТ 17545-72; 500 кВ – по ГОСТ 17544-72; 750 кВ – по ТУ (ТУ 16-517.755-73 для автотрансформатора со средним напряжением 330 кВ, ТУ 16-517.883-75 для автотрансформатора со средним напряжением 500 кВ).
Сведения о трансформаторах тока
Основными параметрами и характеристиками трансформатора тока в соответствии с ГОСТ 7746-78 «Трансформаторы тока. Общие технические требования» являются:
1. Номинальное напряжение – действующее напряжение линейного напряжения, при котором предназначен работать ТТ, указываемое в паспортной таблице трансформатора тока. Для отечественных ТТ принята следующая шкала номинальных напряжений, кВ:
0, 66; 6; 10; 15; 20; 24; 27; 35; 110; 150; 220; 330; 500; 750; 1150.
2. Номинальный первичный ток I1н – указываемый в паспортной таблице ТТ ток, проходящий по первичной обмотке, при котором предусмотрена продолжительная работа ТТ. Для отечественных ТТ принята следующая шкала номинальных первичных токов, А:
1; 5; 10; 15; 20; 30; 40; 50; 75; 80; 100; 150; 200; 300; 400; 500; 600; 750; 800; 1000; 1200; 1500; 2000; 3000; 4000; 5000; 6000; 8000; 10000; 12000; 14000; 16000; 18000; 20000; 25000; 28000; 32000; 35000; 40000.
В трансформаторах тока, предназначенных для комплектования турбо- и гидрогенераторов, значения номинального тока свыше 10000А могут отличаться от приведенных в данной шкале значений.
Трансформаторы тока, рассчитанные на номинальный первичный ток 15; 30; 75; 150; 300; 600; 750; 1200; 1500; 3000 и 6000А, должны допускать неограниченно длительное время наибольший рабочий первичный ток, равный соответственно 16; 32; 80; 160; 320; 630; 800; 1250; 1600; 3200 и 6300А. В остальных случаях наибольший первичный ток равен номинальному первичному току.
1. Номинальный вторичный ток I2н – указываемый в паспортной таблице ТТ ток, проходящий по вторичной обмотке. Номинальный вторичный ток принимается равным 1 или 5А, причем ток 1А допускается только для ТТ с номинальным первичным током до 4000А. По согласованию с заказчиком допускается изготовление ТТ с номинальным вторичным током 2 или 2, 5А.
2. Вторичная нагрузка ТТ Z2н соответствует полному сопротивлению его внешней вторичной цепи, выраженному в Омах, с указанием коэффициента мощности. Вторичная нагрузка может также характеризоваться полной мощностью в вольт-амперах, потребляемой ею при данном коэффициенте мощности и номинальном вторичном токе.
Вторичная нагрузка с коэффициентом мощности cosφ 2 = 0, 8, при которой гарантируется установленный класс точности ТТ или предельная кратность первичного тока относительно его номинального значения, называется номинальной вторичной нагрузкой ТТ Z2н.ном.
Для отечественных трансформаторов тока установлены следующие значения номинальной вторичной нагрузки S2н.ном выраженной в вольт-амперах, при коэффициенте мощности cosφ 2 = 0, 8:
1; 2; 2, 5; 3; 5; 7, 5; 10; 15; 20; 25; 30; 40; 50; 60; 75; 90; 100; 120.
Соответствующие значения номинальной вторичной нагрузки (в Омах) определяются выражением:
Таблица 11
Междуфазные напряжения электрических распределительных сетей трехфазного тока 50Гц
Напряжение, кВ
| номинальное
| наибольшее
| среднее (для расчета токов к.з.)
| 0, 22/0, 127
| -
| 0, 22/0, 127
| 0, 38/0, 22
| 0, 4/0, 23
| 0, 4/0, 23
| 0, 66/0, 38
| 0, 69/0, 4
| 0, 69/0, 4
|
| 3, 5
| 3, 15
|
| 6, 9
| 6, 3
|
| 11, 5
| 10, 5
|
| 23, 0
| 20, 0
|
| 40, 5
| 37, 0
|
| 126, 0
| 115, 0
|
| 172, 0
| 154, 0
|
| 252, 0
| 230, 0
|
| 373, 0
| 330, 0
|
Примечание. Номинальные и наибольшие напряжения указаны по ГОСТ 721-74 и 721-77.
Таблица 12
Допустимый длительный ток для кабелей с алюминиевыми жилами с бумажной пропитанной маслоканифольной и нестекающей массами изоляцией в свинцовой или алюминиевой оболочке, прокладываемых в земле
Сечение токопроводящей жилы, мм2
| Ток, A, для кабелей
| одно-жильных до 1 кВ
| двух-жильных до 1 кВ
| трехжильных напряжением, кВ
| четырех-жильных до 1 кВ
| До 3
|
|
|
| -
|
|
| -
| -
| -
|
|
|
|
|
| -
|
|
|
| ПО
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Продолжение таблицы 12
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| -
|
|
|
|
|
|
| -
|
|
|
| -
|
|
| -
| -
| -
| -
| -
|
|
| -
| -
| -
| -
| -
|
|
| -
| -
| -
| -
| -
|
|
| -
| -
| -
| -
| -
|
|
| -
| -
| -
| -
| -
| Таблица 13